Steril-Aire / UV Resources

UV-C monitoring, interlocks and installation accessories

Choose controls according to the question they answer: lamp status, service hours, UV output or safe access.

Technical content reviewed November 12, 2026 · Tillman & Associates

Monitoring functions are not interchangeable

A useful controls schedule identifies what operators need to know and what action should follow a fault. Separate the indication that a lamp/ballast is operating from elapsed service time, measured UV output and access-door protection.

CU2 senses lamp/ballast current and provides local status plus a remote signal. UV-Repeat combines compatible status signals for remote monitoring. These help operators identify a fault; they do not measure treatment throughout a coil face or an entire airstream.

Hours and UV measurement answer different questions

A lamp hour meter tracks elapsed operation to support replacement planning. It does not directly measure UV energy at the treatment surface.

UV Report uses a sensor to display relative UV output and operating hours. Sensor location and commissioning matter: a reading at one location does not automatically demonstrate the minimum dose everywhere in a system. Tell Tillman whether the requirement is maintenance indication, alarm reporting or an engineered performance measurement.

Access interlocks are part of installation safety

The manufacturer offers a 12 V contact-controller arrangement and a separate hardwired door safety switch. The exact circuit depends on the fixture and installation. Have the installer identify every opening that can expose personnel to the UV system.

The door-switch instructions state that the access switch is secondary protection and must not be used as the main disconnect. A monitoring signal is not a substitute for an interlock. Follow the complete wiring and isolation instructions supplied for the selected equipment.

Prepare a practical controls and accessory schedule

Document the fixture count, power supplies, existing controls and required building-management inputs. Note whether the desired signal is per lamp, per fixture group or a general fault. Signal type, power requirements, enclosure and wiring compatibility must be checked before purchase.

Include mounting/support hardware and service access in the same review. A correctly identified electrical control does not resolve an unsuitable lamp support or an inaccessible service location. For existing systems, send clear label and terminal photographs; do not infer compatibility from a control’s appearance.

What to send Tillman

  • Fixture and power-supply models and quantities
  • Required information: on/off, hours, UV measurement or fault alarm
  • BMS input/signal requirements and intended alarm response
  • Supply power, installation exposure and enclosure needs
  • Access-door count, interlock arrangement and main power isolation
  • Existing controls, wiring labels and mounting/support requirements
Request help from Tillman

Common questions

Does a green lamp-status LED verify disinfection?

No. Operating status and delivered UV dose are different measurements.

Can an access switch serve as the main disconnect?

The manufacturer’s door-switch instructions say it should not. Follow the required separate power-isolation arrangement.

Can all these accessories be used with every UV fixture?

No. Review fixture compatibility, electrical signals, power, enclosure and wiring requirements for the exact assembly.