Monitoring functions are not interchangeable
A useful controls schedule identifies what operators need to know and what action should follow a fault. Separate the indication that a lamp/ballast is operating from elapsed service time, measured UV output and access-door protection.
CU2 senses lamp/ballast current and provides local status plus a remote signal. UV-Repeat combines compatible status signals for remote monitoring. These help operators identify a fault; they do not measure treatment throughout a coil face or an entire airstream.
Hours and UV measurement answer different questions
A lamp hour meter tracks elapsed operation to support replacement planning. It does not directly measure UV energy at the treatment surface.
UV Report uses a sensor to display relative UV output and operating hours. Sensor location and commissioning matter: a reading at one location does not automatically demonstrate the minimum dose everywhere in a system. Tell Tillman whether the requirement is maintenance indication, alarm reporting or an engineered performance measurement.
Access interlocks are part of installation safety
The manufacturer offers a 12 V contact-controller arrangement and a separate hardwired door safety switch. The exact circuit depends on the fixture and installation. Have the installer identify every opening that can expose personnel to the UV system.
The door-switch instructions state that the access switch is secondary protection and must not be used as the main disconnect. A monitoring signal is not a substitute for an interlock. Follow the complete wiring and isolation instructions supplied for the selected equipment.
Prepare a practical controls and accessory schedule
Document the fixture count, power supplies, existing controls and required building-management inputs. Note whether the desired signal is per lamp, per fixture group or a general fault. Signal type, power requirements, enclosure and wiring compatibility must be checked before purchase.
Include mounting/support hardware and service access in the same review. A correctly identified electrical control does not resolve an unsuitable lamp support or an inaccessible service location. For existing systems, send clear label and terminal photographs; do not infer compatibility from a control’s appearance.
What to send Tillman
- Fixture and power-supply models and quantities
- Required information: on/off, hours, UV measurement or fault alarm
- BMS input/signal requirements and intended alarm response
- Supply power, installation exposure and enclosure needs
- Access-door count, interlock arrangement and main power isolation
- Existing controls, wiring labels and mounting/support requirements
Common questions
Does a green lamp-status LED verify disinfection?
No. Operating status and delivered UV dose are different measurements.
Can an access switch serve as the main disconnect?
The manufacturer’s door-switch instructions say it should not. Follow the required separate power-isolation arrangement.
Can all these accessories be used with every UV fixture?
No. Review fixture compatibility, electrical signals, power, enclosure and wiring requirements for the exact assembly.
Technical references
- UV-Repeat technical reference · PDF ↗
Manufacturer technical PDF
- CU2 technical reference · PDF ↗
Manufacturer technical PDF
- 12V Contact Controller technical reference · PDF ↗
Manufacturer technical PDF
- Lamp hour meter technical reference · PDF ↗
Manufacturer technical PDF
- UV Report technical reference · PDF ↗
Manufacturer technical PDF
- Door safety switch technical reference · PDF ↗
Manufacturer technical PDF
Confirm the revision and exact assembly before ordering. This guide supports selection and parts inquiries; use the supplied installation instructions for the work.